Three-phase motor current calculator

Estimate the full-load line current of a three-phase motor from its rated power, supply voltage, power factor and efficiency.

How it is calculated

I = P × 1000 ÷ (√3 × V × PF × η), with P in kW, V line-to-line in volts, PF the power factor and η the efficiency as a fraction.

Worked example

15 kW, 460 V, PF 0.85, η 90 %: I = 15,000 ÷ (1.732 × 460 × 0.85 × 0.90) = 24.61 A.

Steps

  1. Enter the motor output power from the nameplate.
  2. Enter the supply voltage and the power factor and efficiency at full load.
  3. Read the line current and use it to size cable, breaker and overload.

Frequently asked questions

Is this the nameplate FLA?

It is a calculated estimate. Use the nameplate full-load amps for final sizing, since they include the manufacturer test data.

Why does power factor matter?

A lower power factor draws more current for the same kW. Motors at light load have a low PF.

Which current do I use for the breaker?

Size motor branch-circuit conductors for at least 125 % of the full-load current (NEC 430.22), and the protective device per NEC 430.52, or the equivalent rule in your country.

Related calculators

References

Three-phase power relation P = √3 V I PF η; NEC NFPA 70 Article 430 for motor branch-circuit sizing. Confirm against the local electrical code.

Estimates for information only. Verify critical values with a qualified engineer or your supplier standards.