Power factor correction calculator

Calculate the reactive power (kvar) of a capacitor bank needed to improve the power factor of a load.

How it is calculated

Qc = P × (tan φ₁ − tan φ₂), where tan φ = √(1 − PF²) ÷ PF for each power factor.

Worked example

P = 100 kW, PF from 0.70 to 0.95: tan φ₁ = 1.020, tan φ₂ = 0.329, so Qc = 100 × 0.691 = 69.15 kvar.

Steps

  1. Enter the active power from the meter or the load list.
  2. Enter the existing power factor from the bill or power meter.
  3. Enter the target power factor, then read the kvar and round to a standard bank size.

Frequently asked questions

What target PF should I use?

Many utility tariffs penalize a PF below 0.90 to 0.95. Check your tariff before setting the target.

Can I correct to exactly 1.0?

You can, but it can cause overcorrection at light load. Target 0.95 to 0.98 in most plants.

Do I need detuning reactors?

Yes, if there are harmonics from drives or rectifiers. Capacitors alone can resonate with them.

Related calculators

References

Reactive power relation Q = P(tan φ₁ − tan φ₂); IEEE 18 for shunt capacitor standards; utility tariff rules for penalties.